KYORITSU KEW 5410 RCD Tester
Rs. 245,000/-
KYORITSU KEW 5410 RCD Tester price in Pakistan is
Rs. 245,000/-
. W11stop.com has wide range of Industrial Meters with cash on delivery service in Karachi, Lahore, Multan, Peshawar and many other cities.
FEATURES:
- Measurement of RCD trip time Conducting testing
of rated residual non-operating currents at × 1/2 Range, measuring RCD trip time
at × 1 and × 5 Ranges.
- Measurement of trip out current Measuring
trip out current by varying current
automatically.
- Remote Test Enabling a user to hold the Test
Leads with his both hands by locking
the Test Button. Measurement will automatically start when the main voltage is detected.
- Voltage Measurement Carrying out a constant
measurement of voltage in the
range
- stand-by mode at each Range.
- Auto-detection of Contact voltage detecting the voltage to earth of Earth electrodes or protective conductors during RCD
test - when applying test currents - at measurement using EARTH in order
to prevent electrical shocks caused by the damaged earth. Measurement will be
ceased at AC50V or more.
- Dust- and Water-proof dust- and Water-proof
construction(designed to IEC 60529 IP54).
- BacklightFacilitating working at dimly
illuminated locations.
Document:
Product Details | |
Product Name | KYORITSU KEW 5410 RCD Tester |
Price | Rs. 190,000/- |
Computers Specs | |
Rated Voltage | 100V±10%, 200V-10%~+32%, 400V±10%, 50/60Hz |
Display Specification | |
Display | 1999 counts (3 1/2digits), Large LCD |
Summary | |
Applicable standards | IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V IEC 61010-031 IEC 61557-1, 6 IEC 60529 (IP54) |
Included Accessories | 7128A (Test leads) 7129A (Test lead with alligator clip) 8017 (Long pin) × 2 Cord case, 9121 (Shoulder strap), Instruction manual, R6(AA) × 8 |
Operating temperature & humidity range | 0ºC - 40ºC, relative humidity 85% (no condensation) |
Optional Accessories | 7100A (Precision measurement cord set) |
Overload protection | Earth Resistance: 280V AC for 10 seconds across 2 of the 3 terminals Earth Voltage: 300V AC for 1 minute |
Safety Standard | IEC 61010-1 CAT III 300V Pollution Degree 2, IEC 61557 |
Storage temperature & humidity range | -20ºC - 60ºC, relative humidity 85% (no condensation) |
Accuracy | (Measurement of RCD trip time - Measurement of trip out current) (Trip Time) (× 5) 1%rdg±3dgt, (x 1) 1%rdg±3dgt, (x 1/2) 1%rdg±3dgt, (AUTO RAMP mA) Test Current at each step -4%~+4% (Trip Time) (× 5) +2%~+8%dgt, (x 1) +2%~+8%dgt, (x 1/2) -8%~-2%dgt (Voltage Measurement) 2%rdg±4dgt |
Measuring range | Testing time = 0ms~200ms Testing time = 0ms~2000ms Testing time = 0ms~2000ms 40% - 110% of lΔn (goes up by 5%) Testing time 300ms × 15steps (Voltage Measurement) 80V~450V 50/60Hz |
Weight | Approx. 965g (including batteries) |
Insulation Resistance | 50MΩ or more / 1000V (between electrical circuit and enclosure) |
Range | (x 5) (x 1) (x 1/2) (AUTO RAMP mA) |
Test Current (approx.) | 15/30/50/100mA, 15/30/50/100/200/500mA, 15/30/50/100/200/500mA |
Power Source | DC 12V / R6(AA)(1.5V) × 8 |
General Specification | |
Dimensions | 167(L)×186(W)×89(D)mm |