Menu
Your Cart
"Due to currency devaluation, the prices are subject to change without prior notice. Please confirm the price before placing the order."

Circutor CVM-B150 Panel Mounted Power Analyzer

Circutor CVM-B150 Panel Mounted Power Analyzer price in Paksitan
Inquiry
Circutor CVM-B150 Panel Mounted Power Analyzer
  • Stock Availability: Inquiry
  • Model: CIRR-09
Product Views: 6939
Rs. 201,600/-

OVERVIEW:

The CVM-B100 and CVM-B150 units are panel mounted three-phase power analyzers (dimensions: 96x96 and 144x144 mm, respectively). Both offer 4-quadrant measurement (consumption and generation). Suitable for Medium or Low voltage installations, in both 3 or 4-wire three-phase circuits, two-phase circuits with or without neutral, single-phasecircuits or ARON connections.

The CVM-B100 and CVM-B150 high-performance units feature a measurement engine that allows the user to analyse many different electrical parameters, in addition to offering a large variety of optional expansion modules for the same unit.

Features:

  • Format: 96x96 (CVM B100) and 144x144 (CVM B150)
  • High-resolution VGA colour screen
  • IP 65* front panel protection
  • 5 voltage inputs (3 phases + neutral + earth) 1000 Vf-f
  • 4 Current inputs, ITF
  • Class 0.2 voltage and current accuracy
  • Class 0.5S energy accuracy
  • Expandable unit, up to 4 modules, combining digital and analogue outputs, Modbus/TCP, MBus, LonWorks, Profibus, XML/Web
  • Modular (optional addition of expansion modules)
  • Touch-sensitive movement buttons
  • Universal power supply source
  • RS485 communications port (Modbus/RTU and BACnet protocols)
  • Customisation of parameters to be displayed
  • Operating hour indicator for preventive maintenance.
  • Innovative SCV interface (Slide, Choose & View) for versatile data display, enabling the customisation of the parameters displayed on the screen
  • Electrical parameters: instantaneous, maximum, minimum (with date and time) and demand
  • Incremental electrical parameters (energy), times, costs, emissions
  • 3 Tariffs (can be selected via the digital input or RS485 communications)
  • Capable of showing costs and kgCO2 emission sources on the screen, depending on the energy consumed or generated
  • 2 Relay outputs for alarms with delay, times, ON and OFF, etc.
  • 2 transistor outputs for alarms or impulse generation, with all the possible configuration parameters
  • 2 digital inputs, with control over the selection of the unit’s tariffs or configurable for monitoring purposes, with RS-485 Modbus communications, monitoring of logical states of other electromechanical units. (RCCBs, thermal-magnetic circuit breakers, etc.)


Applications:

  • Control and monitoring of all electrical parameters measured in any electric distribution panel and low and high-voltage connection points.
  • 4 alarms (2 per transistor and 2 per relay), fully and independently programmable: low or high value, hysteresis, connection/disconnection delays, normally open or closed standby status and interlocking.
  • Generation of impulses with transistor outputs, fully and independently configurable over any incremental parameter (energy, costs, kgCO2 , total meter or tariff hours)
  • Transducer that converts analogue signals to any instantaneous parameter that the unit can measure or calculate, with built-in expansion modules with analogue outputs.
  • Display of process signals, with a built-in expansion module with analogue inputs; optional reporting of these signals to SCADA systems through communication systems
  • Control of electrical load or alarm signal operations by programming the transistor or relay outputs that are built-in or added through expansion modules.
  • Autonomous datalogger with web server, connected to a M-CVMAB-Datalogger module. Enables direct monitoring of the historical data stored in the unit via a conventional web browser.


Document:

Product Details
Product Name Circutor CVM-B150 Panel Mounted Power Analyzer
Price Rs. 201,600/-
Summary
Voltage range 20 Vp-n - 600 Vp-n (functional, up to 600 Vp-n / 1000 Vp-p)
HARDWARE FEATURES
Input Current .../5A or .../1A .../250mA (MC-ITF)
TECHNICAL SPECIFICATION
AC Consumption min. 4 VA / max. VA (25 VA with all expansion options)
AC Frequency 45...65 Hz
DC Consumption min. 4 VA / max. VA (25 W with all expansion options)
Measurement Margin 2.54 %...120% of the Un for Un=500Vac (p-n)
Power Supply Voltage 100...240 Vac / 120...300 Vdc
Reactive Power 1 ±1 digit (0,05...6 A)
General Specification
Frequency 40 / 70 Hz (360...440 Hz)
Power Circuit 100...240 Vac +/-15% / 100...300 Vdc +/-15%

Write a review

Note: HTML is not translated!
Bad Good