Menu
Your Cart
"Due to currency devaluation, the prices are subject to change without prior notice. Please confirm the price before placing the order."

Schneider 48029 1250 A 3 Pole Air Circuit Breaker

Schneider 48029 1250 A 3 Pole Air Circuit Breaker price in Paksitan
Inquiry
Schneider 48029 1250 A 3 Pole Air Circuit Breaker
  • Stock Availability: Inquiry
  • Model: SCHR-861
Product Views: 6245
Rs. 360,000/-

OVERVIEW:


Breaking Capacity:

  • 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
  • 65 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2

Electrical Durability:

  • 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
  • 10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
  • AC-23A: 10000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
  • AC-23A: 10000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
  • AC-3: 6000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2

Document:

Product Details
Product Name Schneider 48029 1250 A 3 Pole Air Circuit Breaker
Price Rs. 360,000/-
Summary
Ambient Air Temperature for Operation -25…70 °C
Ambient Air Temperature for Storage -40…85 °C
Height 352 mm
Pollution Degree 4 conforming to IEC 60664-1
Rated Current 1250 A at 40 °C
Depth 297 mm
HARDWARE FEATURES
Mounting Mode Fixed
Network Type AC
Number of Poles 3P
Protection Type Without protection
Standards IEC 60947-2
TECHNICAL SPECIFICATION
Rated Impulse Withstand Voltage 12 kV conforming to IEC 60947-2
Rated Insulation Voltage 1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated Service Breaking Capacity 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated Short-Circuit Making Capacity 143 kA 525 V AC at 50/60 Hz 143 kA 690 V AC at 50/60 Hz
General Specification
Control Type Push-button
Mechanical Durability 12500 cycles without maintenance conforming to IEC 60947-2 25000 cycles with maintenance conforming to IEC 60947-2
Network Frequency 50/60 Hz
Width 422 mm

Write a review

Note: HTML is not translated!
Bad Good