Menu
Your Cart

Schneider EZC100H3100 Circuit Breaker MCCB

Schneider EZC100H3100 Circuit Breaker MCCB price in Paksitan
Schneider EZC100H3100 Circuit Breaker MCCB
  • Stock Availability: In Stock
  • Model: SCHR-859
Product Views: 6393
Rs. 10,080/-

OVERVIEW:

Breaking Capacity:

  • 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
  • 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2
  • 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2
  • 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2
  • 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
  • 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2
  • 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 

Rated Service Breaking Capacity:

  • Ics 15 kA 380 V AC 50/60 Hz conforming to IEC 60947-2
  • Ics 5 kA 125 V DC conforming to IEC 60947-2
  • Ics 5 kA 250 V DC conforming to IEC 60947-2
  • Ics 5 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
  • Ics 50 kA 110/130 V AC 50/60 Hz conforming to IEC 60947-2
  • Ics 50 kA 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2
  • Ics 2.5 kA 550 V AC 50/60 Hz conforming to IEC 60947-2
  • Ics 7.5 kA 400/415 V AC 50/60 Hz conforming to IEC 60947-2

Document:

Schneider 3 Poles - 3d Circuit BreakersEasypact - MCCB - EZC100H3100 - TMD - 100 A

Product Details
Product Name Schneider Circuit Breaker - MCCB - EZC100H3100
Price Rs. 10,080/-
Current AC
[In] rated current 100 A ( 40 °C )
Summary
Ambient Air Temperature for Operation -25...70 °C
Ambient Air Temperature for Storage -35...85 °C
Height 130 mm
HARDWARE FEATURES
Depth 60 mm
IK Degree of Protection IK07 conforming to IEC 62262
IP degree of protection IP20 conforming to IEC 60529
Mounting Mode Fixed
Mounting Support Backplate
Network Type AC. DC
Protection Type Short-circuit protection Overload protection
Trip Unit Name TM-D
Trip Unit Rating 100 A ( 50 °C )
Type
product or component type Circuit breaker
General Specification
Connection pitch 25 mm
Control Type Toggle
Earth-Leakage Protection Without
Electrical Durability Category A : 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability 8500 cycles
Network Frequency 50/60 Hz
Poles Description 3P
Protected Poles Description 3t
Range of product EasyPact
Width 75 mm
[Ue] Rated Operational Voltage 250 V DC conforming to IEC 60947-2 550 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947-2
[Ui] rated insulation voltage 690 V AC 50/60 Hz conforming to IEC 60947-2

Write a review

Note: HTML is not translated!
Bad Good