Menu
Your Cart

Schneider Power Factor Controller - VPL12N

Schneider Power Factor Controller - VPL12N  Price in Pakistan
Inquiry
Schneider Power Factor Controller - VPL12N
Rs78,000/-

Available Options

FEATURES:


Varplus logic 12 step

Power factor controller with automatic initialization & automatic detection

Metering type:

voltage U21, U32, U13, V1, V2, V3, on load

Apparent power S, S1, S2, S3, on load

Reactive power Q, Q1, Q2, Q3, on load 

Active power P, P1, P2, P3, on load

Phase current 11, 12, 13 RMS on load

Temperature maximum

Power factor average over lifetime

Total current harmonic distribution THD (I)

Power factor and displacement PF(Signed, Four Quardrant)  


DOCUMENT:


Schneider Power Factor Controller - VPL12N

Product Details
Product NameSchneider Power Factor Controller - VPL12N
PriceRs. 78,000/-
Computers Specs
Color Front : dark grey (RAL 7016)
Display Specification
DisplayBacklit LCD
Display size56 x 25 mm
NameVarPlus Logic
Summary
Ambient Air Temperature for Operation-20...60 °C
FunctionAutomatic initialisation Automatic detection Manual programming Advanced programming (expert) Any step sequence
Height144 mm
Weight0.6 kg
Depth58 mm
Output TypeControl relay : 0.2 A 110 V DC Control relay : 1 A 48 V DC Control relay : 2 A 400 V AC 50/60 Hz Control relay : 1 A 24 V DC Control relay : 5 A 250 V AC 50/60 Hz Control relay : 5 A 120 V AC 50/60 Hz Fan : 5 A 250 V AC 50/60 Hz Fan : 1 A 48 V DC Alarm relay : 5 A 250 V AC 50/60 Hz Alarm relay : 1 A 48 V DC
HARDWARE FEATURES
Input TypeCurrent input CT...X/5 A and X/1 A Insensitive to CT polarity Insensitive to phase rotation polarity Phase to neutral Phase to phase
IP degree of protectionRear face : IP20 Front face : IP41
Mounting ModeFlush-mounted
Supply Voltage90...550 V AC
Width144 mm
MountingIn cabinet
Type
product or component typePower factor controller
UC100
StandardsEN 61010-1 IEC 61000-6-2 IEC 61000-6-4 UL 61010-1 IEC 61326-1
General Specification
ConnectionCommunication protocol: Modbus interface: RS485 `
Contacts12
Type ForMeteringPower factor and displacement PF (signed, four quadrant) Total current harmonic distortion THD (I) Power factor average over lifetime Temperature maximum Phase current I1, I2, I3 RMS on load Active power P, P1, P2, P3 on load Reactive power Q, Q1, Q2, Q3 on load Apparent power S, S1, S2, S3 on load Voltage U21, U32, U13, V1, V2, V3 on load
Alarm Step power loss (< 75 %) / Action: message and alarm contact + step blocked Step faulty / Action: message and alarm contact + step blocked High current (> 6 A CT) / Action: message and alarm contact Hunting (unstable regulation) / Action: message and alarm contact + step blocked Low current (< 15 mA CT) / Action: message and alarm contact Capacitor current overload (Irms/I1) (> 130 % I1) / Action: message and alarm contact + step switched off Overtemperature (50 °C) / Action: message and alarm contact + step switched off Overtemperature (30 °C) / Action: fan switch Overvoltage (+/- 10 %) / Action: message and alarm contact + control stopped Total harmonic distortion (> 7 %) / Action: message and alarm contact + step switched off Overcompensation / Action: message and alarm contact
OTHERS
CertificationsCE EAC NRTL CNRTL

Write a review

Note: HTML is not translated!
Bad Good
Captcha